Brickell
The "dead compressor" was really a cooling-tower water problem
Water-source heat pump on a cooling tower
- Problem
- An hour into a normal run on a weekday afternoon, the compressor tripped and the unit locked itself out.
- How we found it
- Condenser water leaving the unit jumped from 34 to 47 °C in about a minute while the water coming in stayed at 31 °C: the water had stopped moving, so the compressor tripped on high pressure.
- What we did
- Pointed the tech at the water loop instead of the compressor, and added an alert for this exact pattern.
- Result
- Our system now names "loss of condenser water flow" in the alert, about 15 minutes sooner than before.